Product Code: HL-NK1000
Insulating rope tool offering excellent dielectric properties and designed for performing live work on AC or DC energized apparatus.
Meets or exceeds the dry or wet electrical requirements of :
- IEC 62192:2009
- ASTM F1701-12
IEC 62192:2009 | Dry 1 min | Wet 1 min | Wet 5 min |
HL-NK1000 | Pass (~ 87 µA) | Pass (~ 18 µA) | Pass (~ 18 µA) |
Note: Test with no shielding of capacitive currents.
ASTM F1701-12 | Dry | Wet |
HL-NK1000 | Pass (~ 3 µA) | Pass (~ 3 µA) |
Note: Test with shielding of capacitive currents.
Arc-Flash rated
- Resistant to 40 cal/cm2 (category 4)
Features
- Unique insulating properties
- Cleanable and easy to maintain and test
- Exceptionally low leakage current, whether dry or wet
- Protection from high fault current
- High strength
- Low elongation
- Lightweight and low volume
- Fully sealed and hydrophobic
- Smooth surface
- High abrasion resistance
- Easy to deploy
- Excellent resistance to UV
- High visibility sealed termination at each end
- Comes with transport bag
SPECIFICATIONS
- Working Load Limit: 200 lb (90 kg)
- Diameter: 1/4” (6 mm)
- Terminations: Stainless steel thimble at each end
- Colour: Black with bright orange terminations
- Weight:78 lb (0.35 kg) for 20’ length
- Standard Lengths: 20’ (6.1 m), 30’ (9.1 m), 40’ (12.2 m)
Note: Available in other lengths. Contact Barry for more information.